Modulating Dual Fuel Burner
The GI/EMME 1400-4500 series of burners covers a firing range from 407 to 4650 kW. They have been designed for high output users and they are suitable for matching with all kinds of boilers, with normal or pressurized combustion chamber. Operation can be two stage progressive or, alternatively, modulating with the installation of a PID logic regulator and probes. Two operating options, gas or light oil, are available at the touch of a switch. The light oil circuit comes with its own electric motor: so the pump is stopped during gas operation to prevent pump seizure and to avoid oil in circulation. A wide range of accessories and gas trains guarantee maximum working flexibility.
Technical Data
| Model |
GI/EMME 1400 |
GI/EMME 2000 |
GI/EMME 3000 |
GI/EMME 4500 |
| Burner operation mode |
Modulating (with regulator and probes accessories) or two stage progressive |
Modulation ratio at max. output
|
3:1
|
Servomotor
|
run time
|
type
|
SQM 10.16502
|
s
|
42
|
Heat output |
kW
|
407/820-1540
|
581/1163-2325 |
872/1744-3488 |
1163/2350-4650 |
Mcal/h
|
350/705-1324 |
500/1000-2000 |
750/1500-3000 |
1000/2021-4000 |
| Working temperature |
°C min./max.
|
0/40
|
Fuel / Air Data
|
Oil
|
Net calorific value |
kWh/kg
|
11,8
|
| Viscosity |
mm2/s ( cSt)
|
4-6 (at 20°C)
|
| Delivery |
kg/h
|
34/69-130 |
49/99-197 |
74/148-296 |
99/199-394 |
Pump
|
type
|
|
TA2
|
TA3
|
TA4 |
TA5 |
Delivery
|
kg/h
|
336 (at 25 bar)
|
546 (at 25 bar) |
706 (at 25 bar) |
1008 (at 25 bar) |
Atomised pressure
|
bar
|
25
|
Fuel temperature
|
max °C
|
60
|
Fuel preheater
|
NO
|
G20
|
Net calorific value
|
kWh/Nm3
|
10
|
Density
|
kg/Nm3
|
0,71
|
Gas delivery
|
Nm3/h
|
41/82-154
|
58/116-232,5
|
87/174-349
|
116/235-465 |
G25
|
Net calorific value
|
kWh/Nm3
|
8,6
|
Density
|
kg/Nm3
|
0,78
|
Gas delivery
|
Nm3/h
|
47/95-179
|
68/135-270
|
101/203-406
|
135/273-541 |
LPG
|
Net calorific value
|
kWh/Nm3
|
25,8
|
Density
|
kg/Nm3
|
2,02 |
Fan
|
type
|
Centrifugal with reverse curve blades
|
Air temperature
|
max °C
|
60
|
Electrical data
|
Electrical supply
|
Ph / Hz / V
|
3N/50/230-400 (±10%) |
Auxiliary electrical supply
|
Ph / Hz / V
|
1/50/230 (±10%) |
Control box
|
type
|
LFL 1.333
|
Total electrical power
|
kW
|
5,1
|
6,1 |
12
|
15,5 |
Auxiliary electrical power
|
kW
|
1
|
1 |
1,5 |
2 |
Heaters electrical power
|
kW
|
--
|
Protection level
|
IP
|
44
|
Pump motor electrical power
|
kW |
1,1
|
1,1
|
1,5
|
1,5 |
Rated pump motor current
|
A
|
3
|
3 |
3,7
|
3,7 |
Pump motor start up current
|
A
|
--
|
Pump motor protection level
|
IP
|
44 |
Fan motor electrical power
|
kW
|
3
|
4 |
9 |
12 |
Rated fan motor current
|
A
|
6,1
|
8 |
17
|
23 |
Fan motor start up current
|
A
|
44,5
|
64
|
124,1
|
158,7 |
Fan motor protection level
|
IP
|
44
|
44 |
44
|
55 |
Ignition transformer
|
type
|
--
|
V1- V2
|
230 V - 2 x 6 kV
|
I1 - I2
|
1,9 A - 35 mA
|
Operation
|
Intermittent (at least one stop every 24h)
|
Approval Emissions
|
Sound pressure
|
dB(A)
|
85,4
|
88
|
92
|
93,1 |
Sound power
|
W
|
--
|
Oil
|
CO emission
|
mg/kWh
|
< 50
|
Grade of smoke indicator
|
N° Bacharach
|
< 1
|
CxHy emission
|
mg/kWh
|
--
|
NOx emission
|
mg/kWh
|
< 250
|
G20
|
CO emission
|
mg/kWh
|
< 100
|
NOx emission
|
mg/kWh
|
< 150
|
Directive
|
90/396 - 89/336 - 73/23 EEC
|
Conforming to
|
EN 267 - EN 676
|
Certification
|
CE 0085AQ0712
|
CE 0085AQ0712
|
CE 0085AQ0712
|
CE 0085AQ0712 |
DIN 5G830/97 M
|
DIN 5G831/97 M |
DIN 5G832/97 M |
DIN 5G833/97 M |
Reference conditions:
- Temperature: 20°C - Pressure: 1013,5 mbar, Altitude: 100 m a.s.l.
- Noise measured at a distance of 1 meter.
Product SpecificationBurner Mono block forced draught dual fuel burner, two stage progressive or modulating operation with a kit, made up of:
- Air suction circuit
- Fan with forward curved blades
- Air damper for setting and butterfly valve for regulating fuel output controlled by a servomotor
- Combustion head, that can be set on the basis of required output
- Maximum gas pressure switch
- Minimum air pressure switch
- Fan electrical motor
- Pump electrical motor
- Gears pump for high pressure fuel supply, fitted with:
- filter
- pressure regulator
- connections for installing a pressure gauge and a a vacuometer
- internal by-pass for single pipe installation
- Valve unit with a double oil safety valve on the output circuit and safety valve on the return circuit
- UV photocell for flame detection
- Flame inspection window
- Slide bars for easier installation and maintenance
- Protection filter against radio interference
- IP 40 protection level.
Gas train Fuel supply line, in the Multi block configuration from a diameter of 3/4 until a diameter 2 or Composed configuration from a diameter of DN 65 until a diameter of DN 100, fitted with:
- Filter
- Stabilizer
- Minimum gas pressure switch
- Safety valve
- Valve seal control (for output > 1200 kW)
- One stage working valve with ignition gas output regulator.
Conforming to:
- 90/396/EEC directive (gas)
- 89/336/EEC directive (electromagnetic compatibility)
- 73/23/EEC directive (low voltage)
- EN 267 (liquid fuel burners)
- EN 676 (gas fuel burners).
Standard equipment:
- 1 flange (for GI/EMME 1400)
- 1 gas train gasket
- 8 screws for fixing the burner flange to the boiler (for GI/EMME 1400)
- 12 screws for fixing the burner flange to the boiler
- 1 insulating screen
- 2 flexible hoses for connection to the oil supply circuit
- 2 nipples for connection to the pump
- 4 wiring looms fittings for electrical connections
- 2 pin extensions
- 8 washers (for GI/EMME 1400)
- 12 washers
- Instruction handbook for installation, use and maintenance
- Spare parts catalogue.
Available accessories to be ordered separately:
- Return nozzles
- Head length reduction kit
- Sound proofing box
- RWF 40 output regulator
- Pressure probe 0-2,5 bar
- Pressure probe 0-16 bar
- Temperature probe -100-500°C
- Potentiometer kit for the servomotor
- Kit for transformation to LPG
- Gas train adapter
- Stabilizer spring
- Seal control kit.
|