Low NOx Industrial Oil,Gas & Dual Fuel
AirThe industrial burners ER series are designed particularly
for water tube boilers used in big civil installations and industrial
processes with a remarkable thermal demand. These series allows to
realize a modular and flexible combustion system adding a preparation
fuel unit (regulation pressure group set, preheating/pumping oil
station), a gas train, a control panel and a fan. It can also be used a
preheated air as in the oil dia-thermic generators and other heat
recovery systems. The modulating regulation always allows to reach a
wide modulation ratio and optimal fluid dynamics conditions for a good
combustion.
Technical Data
| MODEL |
ER 4 |
ER 6
|
ER 9 |
ER 12
|
ER 16
|
ER 20
|
| Burner operation
mode |
Modulating
|
Modulation ratio at
max. output
|
Natural gas
|
1 : 6 |
LPG
|
1 : 5
|
Light oil
|
1 : 4
|
Heavy oil
|
1 : 3
|
Servomotor
|
run time
|
type
|
MM 10004 - MM 10005
|
s
|
30
|
Heat output |
Natural gas
|
kW
|
540/
2500÷4000
|
840/
4000÷6000 |
1250/
6000÷9000
|
1750/
9000÷12000 |
2350/
12000÷16000
|
3000/
16000÷20000
|
Mcal/h
|
464/
2150÷3440
|
722/
3440÷5160 |
1075/
5160÷7740
|
1505/
7740÷10320
|
2021/
10320÷13760
|
2580/
13760÷17200
|
LPG
|
kW
|
650/
2500÷4000
|
1000/
4000÷6000
|
1500/
6000÷9000
|
2100/
9000÷12000
|
2800/
12000÷16000
|
3600/
16000÷20000
|
Mcal/h
|
559/
2150÷3440
|
860/
3440÷5160
|
1290/
5160÷7740
|
1806/
7740÷10320
|
2408/
10320÷13760
|
3096/
13760÷17200
|
Light oil
|
kW
|
820/
2500÷4000
|
1250/
4000÷6000
|
1870/
6000÷9000
|
2600/
9000÷12000
|
3500/
12000÷16000
|
4500/
16000÷20000
|
Mcal/h
|
705/
2150÷3440
|
1075/
3440÷5160
|
1608/
5160÷7740
|
2236/
7740÷10320
|
3010/
10320÷13760
|
3870/
13760÷17200
|
Heavy oil
|
kW
|
1100/
2500÷4000
|
1700/
4000÷6000
|
2500/
6000÷9000
|
3500/
9000÷12000
|
4700/
12000÷16000
|
6000/
16000÷20000
|
Mcal/h
|
946/
2150÷3440
|
1462/
3440÷5160
|
2150/
5160÷7740
|
3010/
7740÷10320
|
4042/
10320÷13760
|
5160/
13760÷17200
|
| Working temperature |
°C min./max.
|
-15/60
|
|
FUEL/AIR DATE
|
Light
oil
|
Net calorific value |
kWh/kg
|
11,86
|
| Kcal/kg |
10200
|
Viscosity
|
mm2/s (cSt) |
4 ÷ 6 (at 20°C)
|
Delivery
|
kg/h |
69/
211÷337
|
69/
211÷337
|
158/
506÷759
|
219/
759÷1012
|
295/
1012÷1349
|
379/
1349÷1686
|
Fuel temperature
|
max. °C
|
50
|
Heavy
oil
|
Net calorific value
|
kWh/kg
|
11,1÷11,3
|
Kcal/kg
|
9545÷9720
|
Viscosity
|
mm2/s (cSt)
|
500 (at 50°C)
|
Delivery
|
kg/h
|
98/
223÷357
|
152/
357÷536
|
223/
536÷803
|
312/
803÷1071
|
420/
1071÷1428
|
536/
1428÷1786
|
| Fuel temperature |
max. °C
|
140
|
Atomised pressure
|
bar
|
|
G20
|
Net calorific value
|
kWh/Nm3
|
10
|
Density
|
kg/Nm3
|
0,71
|
Gas delivery
|
Nm3/h
|
54/
250÷400
|
84/
400÷600
|
125/
600÷900
|
175/
900÷1200
|
235/
1200÷1600
|
300/
1600÷2000
|
G25
|
Net
calorific value
|
kWh/Nm3
|
8,6
|
Density
|
kg/Nm3
|
0,78
|
Gas delivery
|
Nm3/h
|
63/
291÷465
|
98/
465÷698
|
145/
698÷1047
|
203/
1047÷1395
|
273/
1395÷1860
|
349/
1860÷2326
|
LPG
|
Net calorific value
|
kWh/Nm3
|
25,8
|
Density
|
kg/Nm3
|
2,02
|
Gas delivery
|
Nm3/h
|
25/
97÷155
|
39/
155÷233
|
58/
233÷349
|
81/
349÷465
|
109/
465÷620
|
140/
620÷775
|
Fan
|
type
|
centrifugal with reverse curve blades
|
Air temperature
|
max °C
|
150
|
ELECTRICAL
DATA
|
Electrical supply
|
Ph / Hz / V
|
1/50-60/230 - (1/50-60/110 on request)
|
| Control box |
type
|
--
|
Auxiliary
electrical
supply
|
kW
|
1/50-60/230 - (1/50-60/110 on request)
|
Total current
|
A |
--
|
Protection level
|
IP
|
54
|
Ignition
transformer
|
type
|
ignition pilot burner
|
| V1 - V2 |
230 V - 1x8 kV
|
I1 - I2
|
1,4 A - 30 mA
|
Operation
|
Intermittent (at least one stop every 24 h) - Continuos (at least one stop every 72 h)
|
APPROVAL
EMISSIONS
|
Sound
pressure
|
dB(A)
|
--
|
Sound
power
|
W
|
--
|
Light
Oil
|
CO emission
|
mg/kWh
|
< 110
|
Grade of smoke
indicator
|
N°
Bacharach
|
< 1
|
NOx emission
|
mg/kWh
|
< 185
|
Heavy
Oil
|
CO emission
|
mg/kWh
|
Depending on the
fuel amount
|
Grade of smoke
indicator
|
N° Bacharach
|
Depending on the
fuel amount
|
NOx emission
|
mg/kWh
|
Depending on the
fuel amount
|
G20
|
CO emission
|
mg/kWh
|
< 100
|
NOx emission
|
mg/kWh
|
< 120
|
Directive
|
89/336 - 73/23 - 98/37 - 90/396 EEC
|
Conforming
to
|
EN 267 - EN 676
|
Certification
|
--
|
Reference conditions: Temperature: 20°C - Pressure: 1000 mbar - Altitude: 100 m a.s.l. - Noise measured at a distance of 1 meter.
PRODUCT SPECIFICATION
OIL BURNER
Combustion head:
Forced draught oil burner with modulating operation and separate supplies, fully automatic, made up of:
- sheet-steel airlock painted with a front cover for access to the internal elements
- air dampers for air setting controlled by two Independent high precision servomotors
- combustion head fitted with:
- stainless steel end cone, resistant to corrosion and high temperatures
- pilot burner with gas train and ignition electrodes
- flame stability disk made up of axial swirlers
- flame shape regulation device
- photocell for flame detection
- minimum air pressure switch
- nozzle pipe
- safety nozzle valve
- valves group with safety oil valves
- automatic regulator of oil delivery controlled by a high precision servomotor
- maximum oil pressure switch on the return circuit
- pressure gauge on the delivery circuit
- pressure gauge on the return circuit
- electrical box with ignition transformer
- IP 54 electric protection level.
Conforming to
- 89/336/EEC directive (electromagnetic compatibility)
- 73/23/EEC directive (low voltage)
- 98/37/EEC directive (machinery)
- EN 267 (liquid fuel burners).