Translate In : View in English View in Spanish View in French View in German View in Italian View in Chinese (Simplified) View in Japanese View in Korean View in Arabic View in Portuguese
 
 
 

Home Page
Company Profile
Showroom
Light Oil Burners
Heavy Oil Burners
Industrial Burners & System Components
Gas Burners
Dual Fuel Burners
Water Treatment Plants
 
 
 
 
 
SUNTEC ENERGY SYSTEMS
 
Two Stage Dual Fuel Burner
To inquire, Select Product/s & Click on

Product Code : 09

[Select]
Product Specification
Two Stage Dual Fuel Burner
The GI/EMME 300-900 series of burners covers a firing range from 107 to 922 kW. They have been designed for middle and high output users and they are in particular suitable for matching with pressurized boilers. Their use allow to have an high safety in operation, guaranteed from the double fuel supply.

Two options of operation are available: only gas and only light oil, thus settable by a selector and a terminal board. Light oil circuit is fitted with his own electric motor: this permits pump stop during gas operation preventing danger of pumping seizure. A wide range of accessories and gas trains suitable to the burners guarantee an elevated working flexibility.


Technical Data
Model GI/EMME 300 GI/EMME 400 GI/EMME 600 GI/EMME 900
Burner operation mode Two stage
Modulation ratio at max. output
2:1
Servomotor
run time
type
LKS 210
s
5

Heat output
kW
107/175 - 332
116/232 - 465 174/348 - 665
250/525 - 922
Mcal/h
92/150 - 286
100/200 - 400
150/299 - 572
215/452 - 793
Working temperature °C min./max.
0/40
Fuel / Air Data

Oil
Net calorific value kWh/kg
11,8
Viscosity mm2/s ( cSt)
4-6 (at 20°C)
Delivery kg/h
9/15 - 28
10/20 - 39
15/29 - 56
21/44 - 78
Pump
type

AN 67
AN 67
AN 77
AN 97
Delivery
kg/h
75 at 12 bar
75 at 12 bar
100 at 12 bar
120 at 12 bar
Atomised pressure
bar
12
Fuel temperature
max °C
60
Fuel preheater
NO

G20
Net calorific value
kWh/Nm3
10
Density
kg/Nm3
0,71
Gas delivery
Nm3/h
10,7/17,5 - 33,2
11,6/23,2 - 46,5
17,4/34,8 - 66,5 25/52,5 - 92,2

G25
Net calorific value
kWh/Nm3
8,6
Density
kg/Nm3
0,78
Gas delivery
Nm3/h
12,4/20,3 - 38,6
13,5/27 - 54
20,2/40,4 - 77,3
29/61 - 107,2

LPG
Net calorific value
kWh/Nm3
25,8
Density
kg/Nm3
2,02
Gas delivery
Nm3/h
4,1/6,8 - 12,9
4,5/9 - 18 6,7/13,5 - 25,8
9,7/20,3 - 35,7
Fan
type
Centrifugal with forward curve blades
Air temperature
max °C
60
Electrical data
Electrical supply
Ph / Hz / V
1/50/230 (± 10%)
3N/50/230-400 (±10%)
Auxiliary electrical supply
Ph / Hz / V
1/50/230 (±10%)
Control box
type
LFL 1.333
Total electrical power
kW
0,5
0,62
1,1
2
Auxiliary electrical power
kW
0,1 0,1
0,2
0,35
Heaters electrical power
kW
--
Protection level
IP
44
Pump motor electrical power
kW 0,15
Rated pump motor current
A
1,4
2,85
Pump motor start up current
A
3,2
6,5
Pump motor protection level
IP
44
Fan motor electrical power
kW
0,25
0,37
0,75
1,5
Rated fan motor current
A
1,85 2,9 2,85/1,65
6,55/3,15
Fan motor start up current
A
4,2
6,6
6,5/3,8
32,75/15,75
Fan motor protection level
IP
44

Ignition transformer
type
--
V1- V2
230 V - 1x8 kV
I1 - I2
1,8 A - 30 mA
Operation
Intermittent (at least one stop every 24h)
Approval Emissions
Sound pressure
dB(A)
69
74
82 84
Sound power
W
--


Oil
CO emission
mg/kWh
< 30
Grade of smoke indicator
N° Bacharach
--
CxHy emission
mg/kWh
--
NOx emission
mg/kWh
< 200
G20
CO emission
mg/kWh
< 60
NOx emission
mg/kWh
< 120
Directive
89/336 - 73/23 EEC
Conforming to
EN 267 - EN 676
Certification
--

Reference conditions:
  • Temperature: 20°C - Pressure: 1013,5 mbar - Altitude: 100 m a.s.l.
  • Noise measured at a distance of 1 meter.

Product Specification

Burner:
Monoblock forced draught dual fuel burner, with two-stage operation, made up of:

  • Air suction circuit
  • Fan with forward curved blades
  • Air damper for setting controlled by a servomotor
  • Combustion head, that can be set on the basis of required output
  • Maximum gas pressure switch
  • Minimum air pressure switch
  • Fan electrical motor
  • Pump electrical motor
  • Gears pump for high pressure fuel supply, fitted with:
    • filter
    • pressure regulator
    • connections for installing a pressure gauge and a a vacuometer
    • internal by-pass for single pipe installation
  • Valve unit with a double oil safety valve on the output circuit
  • UV photocell for flame detection
  • Flame inspection window
  • Slide bars for easier installation and maintenance
  • Protection filter against radio interference
  • IP 40 protection level.
Gas train:
Fuel supply line, in the Multiblock configuration from a diameter of 3/4” until a diameter 2 or Composed configuration from a diameter of DN 65 until a diameter of DN 100, fitted with:
  • Filter
  • Stabiliser
  • Minimum gas pressure switch
  • Safety valve
  • Valve seal control (for output > 1200 kW)
  • One stage working valve with ignition gas output regulator.
Conforming to:
  • 89/336/EEC directive (electromagnetic compatibility)
  • 73/23/EEC directive (low voltage)
  • EN 267 (liquid fuel burners)
  • EN 676 (gas fuel burners).
Standard equipment:
  • 1 gas train gasket
  • 1 flange gasket
  • 1 insulating screen
  • 2 flexible hoses for connection to the oil supply circuit
  • 2 nipples for connection to the pump
  • 3 wiring looms fittings for electrical connections
  • 8 screws for fixing the burner flange to the boiler
  • 1 LPG kit
  • Instruction manual for installation, use and maintenance
  • Spare parts catalogue.
Available accessories to be ordered separately:
  • Nozzles
  • Head extension kit
  • Sound proofing box
  • Adapters
  • Stabiliser spring
  • Seal control kit.
Other Products in 'Dual Fuel Burners' category
Modulating Dual Fuel Burner
Modulating Dual Fuel Burner
Two Stage Dual Fuel Burner
Two Stage Dual Fuel Burner
Low NOx Dual Fuel Burner
Low NOx Dual Fuel Burner
 
<< Back
 
 
Contact Details
SUNTEC ENERGY SYSTEMS
Sambhaav House, Nr. Judges Bunglow, Bodakdev, Ahmedabad - 380015, Gujarat, India
Phone:91-79-40009197/40009260/40009261/26871911-13
Fax:91-79-40009196/26871914
Send Mail   Send SMS   
Key Personnel
Ms. Anita Nair (Manager - Co-ordination)
Mobile:+919725343432, +919979774746

 
  
 
Translate In : View in English View in Spanish View in French View in German View in Italian View in Chinese (Simplified) View in Japanese View in Korean View in Arabic View in Portuguese
Copyright © 2009 by SUNTEC ENERGY SYSTEMS All Rights Reserved.