One Stage Gas Burner
The GAS series of burners cover a firing range from 130 to 1050 kW. Operation is one stage; the combustion head, that can be set on the basis of required
output, allows optimal performance ensuring good combustion and reducing fuel consumption.
The GAS series are extremely reliable burners, featured by a simple use and an operation without particular maintenance intervention.
Simplified maintenance is achieved by the slide bar system, which allows easy access to all of the essential components of the combustion head. All electrical components are easily accessible only by dismounting a protection panel, thus guaranteeing a quick and simple intervention on components.
Technical Data
Model
GAS 3
GAS 4
GAS 5
GAS 6
Burner operation mode
One stage
Servomotor
type
run time
s
Heat output
kW
130÷350
185÷465
325÷660
525÷1050
Mcal/h
112÷301
160÷400
280÷570
450÷900
Working temperature
°C min./max.
0/40
Fuel / air data
Net calorific value G20 gas
kWh/Nm3
10
G20 gas density
kg/Nm3
0,71
G20 gas delivery
Nm3/h
13÷35
18,5÷46,5
32,5÷66
52,5÷105
Net calorific value G25 gas
kWh/Nm3
8,6
G25 gas density
kg/Nm3
0,78
G25 gas delivery
Nm3/h
15÷41
22÷54
38÷77
61÷122
Net calorific value LPG gas
kWh/Nm3
25,8
LPG gas density
kg/Nm3
2,02
LPG gas delivery
Nm3/h
5,8÷14
7÷18
13÷26
20÷41
Fan
type
Centrifugal with forward curve blades
Air temperature
Max. °C
60
Electrical data
Electrical supply
Ph/Hz/V
1/50/230~(±10%)
3N/50/400~(±10%) 3/50/230~(±10%)
Auxiliary electrical supply
Ph/Hz/V
1/50/230 ~ (±10%)
Control box
type
RMG
Total electrical power
kW
0,4
0,54
0,85
1,7
Auxiliary electrical power
kW
0,15
0,17
0,1
0,2
Protection level
IP
40
Motor electrical power
kW
0,25
0,37
0,75
1,5
Rated motor current
A
1,8
2,9
2,85÷1,65
5,9÷3,4
Motor start up current
A
4,8
9,5
10÷6
22,5÷13
Motor protection level
IP
54
Ignition transformer
type
V1 - V2
230 V - 1x8 kV
I1 - I2
1,8 A - 30 mA
Operation
Intermittent (at least one stop every 24 h)
Emissions
Sound pressure
dB(A)
75
78
83
84
Sound power
W
CO emission
mg/kWh
< 100
NOx emission
mg/kWh
< 170
Approval
Directive
73/23 - 89/336 - 90/396 - 92/42 EEC
Conforming to
EN 676
Certification
CE 0085AQ0707
Reference conditions
Temperature: 20°C
Pressure: 1013,5 mbar
Altitude: 100 m a.s.l.
Noise measured at a distance of 1 meter.
PRODUCT SPECIFICATION
Burner
Monoblock forced draught gas burner with one stage operation, fully automatic, made up of:
Air suction circuit
Fan with forward curve blades high performance concerning pressure and air delivery
Air damper for air setting
Starting motor at 2800 rpm
Combustion head, that can be set on the basis of required output, fitted with:
Stainless steel end cone, resistant to corrosion and high temperatures
Ignition electrodes
Ionisation probe
Gas distributor
Flame stability disk
Minimum air pressure switch stops the burner in case of insufficient air quantity at the combustion head
Microprocessor-based flame control panel with diagnostic functions
Terminal strip for electrical connections
Slide bars for easier installation and maintenance
Protection filter against radio interference
IP 40 electric protection level.
Gas train
Fuel supply line, in the MULTIBLOC configuration (from a diameter of 3/4 until a diameter 2) or COMPOSED configuration (from a diameter of DN 40 until a diameter of DN 65), fitted with:
Filter
Stabilizer
Minimum gas pressure switch
Safety valve
One stage or two stage working valve with ignition gas output regulator.
Conforming to
89/336/EEC directive (electromagnetic compatibility)
73/23/EEC directive (low voltage)
92/42/EEC directive (performance)
90/396/EEC directive (gas)
EN 676 (gas burners).
Standard equipment:
1 gas train gasket
1 flange gasket
4 screws for fixing the flange
1 thermal screen
4 screws for fixing the burner flange to the boiler
Instruction handbook for installation, use and maintenance
Spare parts catalogue.
Available accessories to be ordered separately:
Extended head kit
Spacer kit
Continuous ventilation kit
Post-ventilation kit
Sound-proofing box
LPG kit
Town gas kit
PC interface kit
Gas train adapter
Stabiliser spring
Seal control kit.
Other Products in 'Gas Burners' category
Modulating Gas Burners
Low NOx Two Stage Modulating Gas Burner
<< Back
Contact Details
SUNTEC ENERGY SYSTEMS
Sambhaav House, Nr. Judges Bunglow, Bodakdev, Ahmedabad - 380015, Gujarat, India
Phone:
91-79-40009197/40009260/40009261/26871911-13
Fax:
91-79-40009196/26871914
Send Mail
Send SMS
Contact Now
Send E-mail
Call Me Free
Key Personnel
Ms. Anita Nair (Manager - Co-ordination)
Mobile:
+919979774746, +919725343432
Translate In :
Copyright © 2009 by SUNTEC ENERGY SYSTEMS All Rights Reserved.